🧾 DETAILED NOTES
1️⃣ Introduction
Lightning strikes are one of the most unpredictable and destructive natural phenomena. In mining areas, lightning can cause electrical surges, fires, explosions, and fatal accidents, especially around coal stockyards, oil storage tanks, and mine substations. To minimize such hazards, every surface installation in mines must be protected by a Lightning Protection System (LPS) designed and maintained as per DGMS circulars and Indian Standards (IS/IEC 62305).
2️⃣ DGMS and Statutory Provisions
| Regulation / Standard | Description |
|---|---|
| CMR 2017 – Reg. 131A | Mandates protection against lightning in surface and underground installations. |
| DGMS Circular 1 of 2016 | Guidelines for design, testing, and maintenance of lightning protection systems. |
| DGMS Circular 3 of 2018 | Specifies periodic testing and resistance limits for earthing systems. |
| IS/IEC 62305 (Part 1–4) | Indian Standard for lightning protection design and risk management. |
| Mines Act, 1952 – Sec. 18 | Safety in electrical installations including lightning. |
3️⃣ Purpose of Lightning Protection System (LPS)
- Protect human life and mine property.
- Prevent fire or explosion in areas storing coal dust, fuel, or explosives.
- Provide safe discharge path for lightning energy to earth.
- Avoid electrical surges damaging communication and control systems.
4️⃣ Components of LPS
| Component | Function |
|---|---|
| Air Terminal (Lightning Rod) | Captures the lightning strike. |
| Down Conductor | Conducts discharge current to the earth. |
| Earth Electrode (Earth Pit) | Safely dissipates energy into the ground. |
| Bonding Conductors | Equalize potential to prevent side flashing. |
| Surge Protection Device (SPD) | Protects sensitive electrical equipment from voltage spikes. |
5️⃣ Installation Guidelines
- LPS must cover all exposed structures like offices, sub-stations, magazines, fuel storage, headgear, workshops, etc.
- Lightning conductor should extend at least 3 m above the structure.
- Earth resistance should not exceed 10 ohms under dry conditions.
- Down conductors must be installed symmetrically for proper current distribution.
- All joints and clamps must be mechanically strong and corrosion resistant.
- Separate earthing pits should be used for lightning and power systems.
- Testing terminal must be provided for each electrode.
6️⃣ Maintenance and Testing
- Visual inspection: Every 3 months before monsoon.
- Testing: Earth resistance to be tested once every six months.
- Recording: Test results must be entered in the Lightning Protection Register.
- Repairs: Damaged rods, corroded joints, or broken conductors must be replaced immediately.
- DGMS Compliance: Annual inspection certificate to be submitted to DGMS electrical region.
7️⃣ Common Hazards Without LPS
- Fire in coal stacks or explosive stores.
- Electric shock to workers.
- Damage to electrical circuits and communication systems.
- Fatal strikes near headgear or conveyors.
⚙️ QUICK ONE-LINERS (Revision Points)
- CMR Reg. 131A – Protection against lightning.
- IS/IEC 62305 – Lightning protection design standard.
- Earth resistance ≤ 10 ohms.
- DGMS Circular 1/2016 – LPS design & testing.
- DGMS Circular 3/2018 – Earthing resistance measurement.
- Lightning rods must be ≥ 3 m above structure.
- Separate earthing for lightning and power.
- Half-yearly testing mandatory.
- Register must record results & inspection dates.
- Surge protection devices (SPD) safeguard electronics.
🧩 DESCRIPTIVE MODEL QUESTION
Q. Describe the design, installation, and maintenance requirements of a Lightning Protection System (LPS) in mines as per DGMS guidelines.
Answer:
As per CMR 2017 Reg. 131A and DGMS Circular 1/2016, every surface installation in mines must have an LPS. It comprises air terminals, down conductors, and earth electrodes connected by copper or GI strips. The lightning rod must rise at least 3 m above the highest point, and the earth resistance should not exceed 10 ohms. All systems must be tested half-yearly (every 6 months) and recorded in the Lightning Protection Register. Proper LPS prevents fire, shock, and equipment damage from lightning strikes.
🧮 25 DGMS-Based MCQs (5 Options Each)
Q1. Regulation dealing with lightning protection in mines:
Q2. DGMS Circular for lightning protection system:
Q3. Standard followed for LPS design:
Q4. Maximum permissible earth resistance for LPS:
Q5. Frequency of LPS testing:
Q6. Lightning conductor height above structure:
Q7. Earth electrodes for lightning should be:
Q8. LPS includes:
Q9. Lightning counter used to:
Q10. DGMS Circular 3/2018 refers to:
Q11. Lightning energy dissipated through:
Q12. Material commonly used for down conductor:
Q13. LPS register maintained by:
Q14. DGMS mandates testing interval of:
Q15. Equipotential bonding prevents:
Q16. LPS protects against:
Q17. Recommended earthing conductor size (minimum):
Q18. LPS resistance measured with:
Q19. Testing terminal provided for:
Q20. LPS failures often due to:
Q21. Standard for risk assessment in LPS:
Q22. Earth pit identification must include:
Q23. LPS should be inspected before:
Q24. Surge Protection Devices are connected at:
Q25. DGMS-approved LPS ensures:
🔗 INTERNAL LINKS
| Related Topic | Read More On... |
|---|---|
| Electrical Safety | Electrical Safety & Accident Investigation |
| Electrical Training | DGMS Training Syllabus for Electrical Engineers |
| CMR 2017 | CMR 2017 Part 2 - Working & Supervision Rules |
| DGMS Circulars | DGMS General Circular No. 01 of 2023 |
⚡ Crack DGMS Exams with Expert Notes & 25 MCQs!
Master Lightning Protection System design, DGMS rules, and electrical safety standards with Online Mining Exam – India’s 1st Online Mining Academy.
- Detailed Electrical Safety Notes
- DGMS Circulars Explained
- 5000+ Topic-wise MCQs
🌐 Visit: www.onlineminingexam.com
📞 Call/WhatsApp: 9971114020

